Oil-Immersed Power Transformer 33kv 11kv
Oil-Immersed Power Transformer 33kv 11kv image
Get Latest Price Request a quote
Quick Details
Product Details
Suzhou Silverstone Electric Co., Ltd
1. General
(1) Application:
>> 12, 24,36KV~220kv class transformers
are widely used in power transmission and distribution stations,
industry plants, Generation Setup Unit (GSU).
>> They have the characteristic of high efficiency, low loss and maintenance free.
(2) Type and Rating
**Capacity range :50-50000KVA.
**Secondary voltage: 415V ,400V etc.
**Frequency :50Hz ,60Hz.
**Type: Single phase, three phase.
**No-load tap changer and on-load tap changer.
**ONAN and ONAF.
**Set-up and set-down type.
(3) Standard: IEC60076-1, IEC60076-2, IEC60076-5, IEC60317, ANSI, IEEE, AS, etc.
2. Conditions of service
(1) Altitude: Up to 1,000m above sea level.
(2) Ambient temperature:
**Max: +40ºC.
**Average (daily, Max.): +30ºC.
**Average (yearly, Max.): +20ºC.
**Min: -45ºC.
(3) Environment: Outdoor.
(4) Special conditions:
It may be consulted between manufacturer and customer.
3. Structural Features
(1) Iron core
The iron core is made of cold rolled grain oriented silicon steel sheet. Laminations are cut to length
on GEORG cut to- length line with step lap cut and automatic stacking functions.
The multistep lamination structure can reduce the loss and noise.
The steel sheet in the core limbs and yokes are clamped together by glass-epoxy bonds.
(2) Winding
High quality enameled or paper covered copper is used as conductor, the winding was made as
drum type, spiral type, improved spiral type, continuous type and interleaved type to ensure the insulation strength. Standard tapings are ±2*2.5%of the HV winding.
(3) Tank
The tank, cover and the conservator are made by corrugated steel plate. For the small transformers,
we use a deep tank and a cover, but for larger transformers, we manufacture bell type. The corrugated construction is a effective way for oil cooling.
(4) Insulation oil
The tanks are filled with high quality grade mineral oil as per IEC296 and it is PCB and PCT free.
The oil is used to help cooling the transformer. It is also used provide part of the electrical insulation between internal live parts.
(5) Tap changer
Tap changers are used to regulate the output voltage of the transformers to required levels. We
achieve this by changing the ratios of the transformer on the system by altering the number of turns in the HV winding. Tap changers can be on load (OLTC) or off load(OCTC).
(6) Assembly
The core and the windings assembled together from the active part of the transformer. The active
body assembled with multi-windings and identical pressure dry method adopted, effectively improved
the electrical strength and the ability to short circuit withstanding.
4. Test equipment
Strict test should be done according to IEC standard, by high technical equipment to ensure the
quality and the reliable of every transformer.
5. Technical Data of Typical Products
>S9, S10 series 10KV three phase off -load tap changer distribution transformer
| Type | Rating KVA |
On-load loss (w) |
Load loss (w) |
I (%) |
UK (%) |
Dimension (mm) | Weight (kg) |
||
| a | b | c | |||||||
| S9-M-50/11 | 50 | 170 | 870 | 2.0 | 4.0 | 1215 | 660 | 1170 | 430 |
| S9-M-250/11 | 250 | 560 | 3050 | 1.2 | 4.0 | 1190 | 815 | 1370 | 1115 |
| S9-M-400/11 | 400 | 800 | 4300 | 1.0 | 4.0 | 1515 | 770 | 1580 | 1380 |
| S9-M-500/11 | 500 | 960 | 5050 | 1.0 | 4.0 | 1635 | 840 | 1610 | 1600 |
| S9-M-1000/11 | 1000 | 1700 | 10300 | 0.7 | 4.5 | 1960 | 1095 | 1960 | 2860 |
| S9-M-2500/11 | 2500 | 3300 | 23000 | 0.55 | 5.5 | 2230 | 2305 | 2445 | 5660 |
| S10-M-30/10 | 30 | 110 | 600 | 1.8 | 4.0 | 870 | 645 | 1025 | 310 |
| S10-M-50/10 | 50 | 140 | 870 | 1.7 | 4.0 | 1090 | 650 | 1080 | 395 |
| S10-M-80/10 | 80 | 200 | 1250 | 1.6 | 4.0 | 1140 | 675 | 1110 | 490 |
| S10-M-100/10 | 100 | 240 | 1500 | 1.5 | 4.0 | 1185 | 690 | 1130 | 560 |
| S10-M-125/10 | 125 | 280 | 1800 | 1.4 | 4.0 | 1205 | 710 | 1180 | 670 |
| S10-M-160/10 | 160 | 340 | 2200 | 1.3 | 4.0 | 1255 | 720 | 1200 | 780 |
| S10-M-200/10 | 200 | 400 | 2600 | 1.2 | 4.0 | 1295 | 740 | 1215 | 875 |
| S10-M-250/10 | 250 | 470 | 3050 | 1.1 | 4.0 | 1340 | 755 | 1260 | 1115 |
| S10-M-315/10 | 315 | 560 | 3650 | 1.0 | 4.0 | 1400 | 770 | 1320 | 1280 |
| S10-M-400/10 | 400 | 680 | 4300 | 0.9 | 4.0 | 1500 | 860 | 1400 | 1490 |
| S10-M-500/10 | 500 | 810 | 5150 | 0.9 | 4.0 | 1575 | 895 | 1430 | 1740 |
| S10-M-630/10 | 630 | 1020 | 6200 | 0.8 | 4.5 | 1660 | 930 | 1545 | 2110 |
| S10-M-800/10 | 800 | 1190 | 7500 | 0.7 | 4.5 | 1830 | 1070 | 1590 | 2625 |
| S10-M-1000/10 | 1000 | 1450 | 10300 | 0.6 | 4.5 | 1935 | 1175 | 1685 | 2860 |
| S10-M-1250/10 | 1250 | 1650 | 12000 | 0.6 | 4.5 | 1960 | 1170 | 1730 | 3330 |
| S10-M-1600/10 | 1600 | 2040 | 14500 | 0.5 | 4.5 | 2325 | 1220 | 2120 | 3765 |
| S10-M-2000/10 | 2000 | 2140 | 17820 | 0.5 | 4.5 | 2395 | 1260 | 2225 | 4530 |
>>S11 series 20KV three phase off -load tap changer distribution transformer
| TYPE | Voltage ratio(kV) | Connection | No load Loss (W) |
Load loss (W) |
Io (%) |
UK (%) |
Dimensions (mm) | Weight (Kg) | |||||
| a | b | c | d | e | f | ||||||||
| S11-M-30/20 | 20(10) ±5%/0.4 |
Yyn0 Dyn11 |
100 | 690/ 660 |
2.1 | 5.5 |
1100 | 700 | 1240 | 14 | 400 | 400 | 640 |
| S11-M-50/20 | 130 | 1010/ 960 |
2.0 | 1130 | 710 | 1260 | 14 | 400 | 450 | 710 | |||
| S11-M-63/20 | 150 | 1200/1150 | 1.9 | 1160 | 740 | 1270 | 14 | 400 | 450 | 780 | |||
| S11-M-80/20 | 180 | 1440/1370 | 1.8 | 1200 | 770 | 1280 | 14 | 400 | 450 | 860 | |||
| S11-M-100/20 | 200 | 1730/ 1650 |
1.6 | 1220 | 800 | 1300 | 14 | 400 | 450 | 900 | |||
| S11-M-125/20 | 240 | 2080/ 1980 |
1.5 | 1270 | 840 | 1330 | 19 | 550 | 450 | 970 | |||
| S11-M-160/20 | 290 | 2540/ 2420 |
1.4 | 1320 | 870 | 1350 | 19 | 550 | 550 | 1100 | |||
| S11-M-200/20 | 340 | 3000/ 2860 |
1.3 | 1360 | 900 | 1380 | 19 | 550 | 550 | 1240 | |||
| S11-M-250/20 | 400 | 3520/ 3350 |
1.2 | 1430 | 910 | 1430 | 19 | 550 | 650 | 1420 | |||
| S11-M-315/20 | 480 | 4210/ 4010 |
1.1 | 1460 | 920 | 1450 | 19 | 550 | 650 | 1570 | |||
| S11-M-400/20 | 570 | 4970/ 4730 |
1.0 | 1490 | 940 | 1470 | 19 | 660 | 750 | 1740 | |||
| S11-M-500/20 | 680 | 5940/ 5660 |
1.0 | 1570 | 970 | 1540 | 19 | 660 | 750 | 1950 | |||
| S11-M-630/20 | 810 | 6820 | 0.9 | 6.0 |
1650 | 1000 | 1580 | 19 | 660 | 850 | 2290 | ||
| S11-M-800/20 | 980 | 8250 | 0.8 | 1750 | 1070 | 1650 | 19 | 820 | 850 | 2690 | |||
| S11-M-1000/20 | 1150 | 11330 | 0.7 | 1830 | 1170 | 1690 | 19 | 820 | 850 | 2880 | |||
| S11-M-1250/20 | 1380 | 13200 | 0.7 | 1900 | 1200 | 1790 | 19 | 820 | 850 | 3400 | |||
| S11-M-1600/20 | 1660 | 15950 | 0.6 | 1950 | 1250 | 1850 | 19 | 820 | 900 | 4100 | |||
>>>>S9 series 35kV three phase Off-load tap changer power transformer
| Capacity KVA |
Voltage and tap range | Connection | No-load loss (kW) |
Load loss (KW) |
NO-load current (%) |
Impedance (%) |
Dimensions (mm) LxWxH |
||
| HV (kV) | MV (kV) | LV (kV) | |||||||
| 50 | 35 | ± 5 | 0.4 | Dyn11 Yyn0 |
0.21 | 1.27/1.21 | 2.00 | 6.5 | 1100x845x1715 |
| 100 | 0.29 | 2.12/2.02 | 1.80 | 1190x915x1780 | |||||
| 125 | 0.34 | 2.50/2.38 | 1.70 | 1220x1040x1780 | |||||
| 160 | 0.36 | 2.97/2.83 | 1.60 | 1240x1070x1810 | |||||
| 200 | 0.43 | 3.50/3.33 | 1.50 | 1380x780x1875 | |||||
| 250 | 0.51 | 4.16/3.96 | 1.40 | 1540x880x1820 | |||||
| 315 | 0.61 | 5.01/4.77 | 1.40 | 1440x800x1975 | |||||
| 400 | 0.73 | 6.05/5.76 | 1.30 | 1660x825x1995 | |||||
| 500 | 0.86 | 7.28/6.93 | 1.20 | 1710x865x2030 | |||||
| 630 | 1.04 | 8.28 | 1.10 | 1630x1235x2070 | |||||
| 800 | 1.23 | 9.90 | 1.00 | 1655x1415x2120 | |||||
| 1000 | 1.44 | 12.15 | 1.00 | 1860x1435x2220 | |||||
| 1250 | 1.76 | 14.67 | 0.90 | 1890x1640x2260 | |||||
| 1600 | 2.12 | 17.55 | 0.80 | 2050x1720x2390 | |||||
| 630 | 3.15 6.3 10.5 |
Yd11 | 1.04 | 8.28 | 1.10 | 1630x1235x2070 | |||
| 800 | 1.23 | 9.90 | 1.00 | 1655x1415x2120 | |||||
| 1000 | 1.44 | 12.15 | 1.00 | 1860x1435x2220 | |||||
| 1250 | 1.76 | 14.67 | 0.90 | 1890x1640x2260 | |||||
| 1600 | 2.12 | 17.55 | 0.80 | 2050x1720x2390 | |||||
| 2000 | 2.72 | 19.35 | 0.70 | 2400x1900x2410 | |||||
| 2500 | 3.20 | 20.70 | 0.60 | 2500x1930x2700 | |||||
| 3150 | 35~ 38.5 |
± 5 | 3.15 6.3 10.5 |
3.80 | 24.30 | 0.56 | 7.0 | 2600x2100x2800 | |
| 4000 | 4.52 | 28.80 | 0.56 | 2830 x2350x2855 | |||||
| 5000 | 5.40 | 33.03 | 0.48 | 2930x2480x2930 | |||||
| 6300 | 6.56 | 36.90 | 0.48 | 7.5 | 3150x2330x3220 | ||||
| 8000 | ± 2 x 2.5 | 3.15 3.3 6.3 6.6 10.5 11 |
YNd11 | 9.00 | 40.50 | 0.42 | 3295x3110x3345 | ||
| 10000 | 10.88 | 47.70 | 0.42 | 3450x3210x3440 | |||||
| 12500 | 12.60 | 56.70 | 0.40 | 8.0 | 3620x3255x3500 | ||||
| 16000 | 15.20 | 69.30 | 0.40 | 3980x3420x3650 | |||||
| 20000 | 18.00 | 83.70 | 0.40 | 4030x3470x3690 | |||||
| 25000 | 21.28 | 99.00 | 0.32 | 5050x4640x3930 | |||||
| 31500 | 25.28 | 118.8 | 0.32 | 5120x4800x4030 | |||||
>>>>S9 series 35kV three phase on-load tap changer power transformer
| Type | Voltage compose and Tapping range (kV) | Connection |
No-load Loss (kW) |
Load loss (kW) |
No- load current (I%) |
Impedance voltage (%) | Transport weight (t) | Gross weight (t) | Dimensions L×W×H (mm) |
|
| HV | LV | |||||||||
| SZ9-2000/35 | 35 ±3×2.5% |
6.3 10.5 |
Yd11 | 2.88 | 18.7 | 1.00 | 6.5 | 4.93 | 5.97 | 3010×2070×2540 |
| SZ9-2500/35 | 3.40 | 21.7 | 1.00 | 6.5 | 5.68 | 6.95 | 3040×2270×2610 | |||
| SZ9-3150/35 | 4.04 | 26.0 | 0.90 | 7.0 | 6.08 | 7.90 | 3160×2300×2640 | |||
| SZ9-4000/35 | 35 38.5 ±3×2.5% |
6.3 10.5 |
4.84 | 30.7 | 0.90 | 7.0 | 7.10 | 9.11 | 3300×2330×2890 | |
| SZ9-5000/35 | 5.80 | 36.0 | 0.85 | 7.0 | 8.47 | 10.86 | 3350×2520×3000 | |||
| SZ9-6300/35 | 7.04 | 38.7 | 0.85 | 7.5 | 9.87 | 12.30 | 3680×2650×3050 | |||
| SZ9-8000/35 | 9.84 | 42.8 | 0.75 | 7.5 | 12.55 | 15.30 | 4190×2930×3280 | |||
| SZ9-10000/35 | 35 38.5 ±3×2.5% |
6.3 6.6 10.5 11 |
Ynd11 |
11.6 | 50.6 | 0.75 | 7.5 | 14.70 | 17.86 | 4620×3160×3400 |
| SZ9-12500/35 | 13.7 | 60.0 | 0.70 | 8.0 | 17.35 | 20.05 | 4740×3200×3540 | |||
| SZ9-16000/35 | 16.0 | 73.0 | 0.70 | 8.0 | 19.45 | 23.74 | 4810×3360×3790 | |||
| SZ9-20000/35 | 18.9 | 88.3 | 0.70 | 8.0 | 27.50 | 34.95 | 4880×3540×4150 | |||
| SZ9-25000/35 | 22.4 | 104.4 | 0.65 | 8.0 | 32.51 | 40.22 | 4920×3920×4200 | |||
| SZ9-31500/35 | 26.6 | 125.3 | 0.65 | 8.0 | 37.73 | 45.53 | 5010×4270×4460 | |||
We are China Oil-Immersed Power Transformer 33kv 11kv manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Oil Transformet Products
Sc (H) 11-30~500kVA 10kv Distribution Transformers
Three Phase Pad Mounted Live Front Distribution Transformer
230kv 132kv Oil-Immersed Power Transformer IEC Standard
230kv 132kv 126kv Oil-Immersed Power Transformer IEC Standard
Pad Mounted Compact Type Three Phase Distribution Transformer
11kv 30~1000kVA Dimensions with Protection Enclosure
Popular Power Transformer Products
110kv and Above Rectifier Special Transformer
1250kVA 6.6kv 0.4kv Distribution Transformer Power Transformers
33kv 100mva Three Phase Oil Immersed Furnace Transformer Special Transformer
Step Voltage Regulator 11kv Voltage Stabilizer
Energy Saving Delta Core Oil Immersed Power Transformer
Pad Mount Three Phase Live Front Distribution Transformer
Popular Rectifier Transformer Products
Traction Transformer 132kv 126kv 110kv Tap Changing Oltc IEC Standard
132kv Level and Below Furnace Transformer with Tap Changing Oltc
33kv Rectifier Special Transformer
Rectifier Special Transformer 11kv 33kv
210kVA DC185V Cast Resin Insulation Dry Type Excitation Rectifier Transformer
132kv Furnace Transformer with Tap Changing Oltc
Popular silverstone-electric Products
Dry Type 33kv Power Transformers with on-Load Tap Changer
10kv 11-33kv Sc (H) 11-30~500kVA Distribution Transformers
Manufacture 2500kVA 33kv Distribution Transformers
Rogowski Series Split Core Current Transformers
Transformer Porcelain Bushing for Transformer/Busbar
24kv Pin Type Post Porcelain Ceramic Insulator
Tags: Oil Transformet, Power Transformer, Rectifier Transformer, silverstone-electric