Smart Neutral Grounding Resistor, Intelligent Resistor Monitoring Device
Smart Neutral Grounding Resistor, Intelligent Resistor Monitoring Device image
Get Latest Price Request a quote
Basic Info.
Product Description
Features
FM160 intelligent resistor monitoring device during normal system operation can be monitored when the neutral
unbalance current, resistor temperature (the highest temperature up to 1000 ºC); single-phase ground fault,
can record instant resistance, grounding time, sheet resistance temperature changes and ground operation
frequency and RS485 communication interface, MODBUS protocol to be seized. Measured, recorded
information is transmitted to the control room or computer unit, remote control. Intelligent control section in strict
accordance with the implementation of the relevant national standards for manufacturing.
Neutral grounding resistors are made of special stainless steel electric-heat metal imported from US.They are
with outstanding characters such as high temperature-resistant capability,excellent anti-oxidation
performance,strong tensile characteristics,high resistivety and stable resistance value,what’s more,it can
sustain elec-tric and thermodynamic performance even under 1000°C,which enables safe and reliable
operation.
According to different connection mode or various customer requests,we can provide epoxy resin to cast dry
type transformers,zero sequence current transformers,single-phase discon-necting switches,heater and
thermo/humidity controllers etc.
Voluntary Standards
DL/T780-2001 Neutral grounding resistors in electric power distribution system
GB6450 Dry type Electric transformer
DL/T620-1997 Over-voltage protection and insulation coordination for AC equipment
GB/T16927-1997 High-voltage testing technology
GB1208-1997 Current transformer
GB4208-1993 Protection level of enclosure(IP Code)
IEE32-1972 Technology,terms and test of neutral grounding resistors
GB311.1-1997 Insulation coordination of high-voltage transmitting and distribution equipment
DL/T593-1996 Common order technical requirements of high- voltage switch equipment
GB/T11022-1999 Electric equipment delivery testing criterion of electric device installation Other national
criterion and electric power industry standards.
Operation Environment
Air Temperature:≥-35°C,≤+50°C
Altitude:≤1000m(general)
Wind pressure: ≤700 Mpa(equal to wind speed at 34 m/s)
Earthquake intensity: ≤magnitude 8
lce cover: ≤15mm
Air contamination level:≤IV
Product Categories
The low resistance grounding resistor for electric power distribution networks
The moderate resistance grounding resistor for electric power distribution networks
The high resistance grounding resistor for electric power distribution networks
The high resistance grounding resistor for generators
Parameters of products
Voltage:0.4kV~110kV;
Rated current:optional;
Nominal resistance:optional;
Current duration:10s,30s,60s,10min,continuous;
Incoming and outing line:top in bottom out,bottom in bottom out,side in side out,side in bottom out,etc;
Installation site:indoor/outdoor;
Allowable temperature rise:760°C for 10s,30s,60s and 610°Cfor 10min and 385°C for continuous
Zero sequence current transformer:optional
| Type | Rated Voltage of system | Rated Voltage of resistor | Rated current | Current duration | (Ω) ±10% Nominal resistance value | W×D×H (mm) Dimension | (kg) Weight |
| NGR-6.3/100-10 | 6.3 | 3.64 | 100 | 10 | 36.4 | 1300 ×1300 ×1900 | 450 |
| NGR-6.3/200-10 | 6.3 | 3.64 | 200 | 10 | 18.2 | 500 | |
| NGR-6.3/400-10 | 6.3 | 3.64 | 400 | 10 | 9.09 | 500 | |
| NGR-6.3/600-10 | 6.3 | 3.64 | 600 | 10 | 6.06 | 500 | |
| NGR-6.3/1000-10 | 6.3 | 3.64 | 1000 | 10 | 3.64 | 500 | |
| NGR-10/100-10 | 10 | 5.77 | 100 | 10 | 57.7 | 500 | |
| NGR-10/200-10 | 10 | 5.77 | 200 | 10 | 28.9 | 550 | |
| NGR-10/400-10 | 10 | 5.77 | 400 | 10 | 14.4 | 550 | |
| NGR-10/600-10 | 10 | 5.77 | 600 | 10 | 9.62 | 550 | |
| NGR-10/1000-10 | 10 | 5.77 | 1000 | 10 | 5.77 | 550 | |
| NGR-20/600-10 | 20 | 11.5 | 400 | 10 | 28.9 | 1700 ×1700 ×2600 | 1250 |
| NGR-20/600-10 | 20 | 11.5 | 600 | 10 | 19.2 | 1250 | |
| NGR-35/200-10 | 35 | 20.2 | 200 | 10 | 101 | 3000 ×1700 ×2600 | 2000 |
| NGR-35/400-10 | 35 | 20.2 | 400 | 10 | 50.5 | 2000 | |
| NGR-35/600-10 | 35 | 20.2 | 600 | 10 | 33.7 | 2000 | |
| NGR-35/1000-10 | 35 | 20.2 | 1000 | 10 | 20.2 | 2000 | |
| NGR-35/1300-10 | 35 | 20.2 | 1300 | 10 | 15.5 | 3000 ×1700 ×3100 | 2500 |
| NGR-35/2000-10 | 35 | 20.2 | 2000 | 10 | 10.1 | 250 |
Packaging & Shipping
Packing, Transportation, Storage
The package should be placed on sleeper by normal position and fastened by bolt;
The cabinet should be covered with foam to be protected against dust and vapor during the transportation;
Keep the equipment in its original package when deliver to installation field, so as to prevent it from possible
damage during the transportation;
Fix it with fastener to prevent it from resistor looseness during the transportation;
Seal the box with lath;
Indicate delivery place, equipment name, weight etc on the packing box clearly;
All the boxes can be lifted to the common container by forklift;
Unload the goods with forklift or crane after its arrival;
Inspect the goods after unloading to make sure that the goods is in good condition.
kaging & Shipping
Packaging Details:each in foam box or Packaging Details:
wooden pakage
Thanks for choosing VILLE as your reliable partner and
please trust both of us will create a brilliant future!
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(“,”).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
We are China Smart Neutral Grounding Resistor, Intelligent Resistor Monitoring Device manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular cnville Products
Lvb-220 Series Oil Immersed Inverted Current Transformers
200kVA 20kv Wound Core Type Hermetically Sealed Oil Immersed Transformers Distribution Transformer
Sf10-31500/110 31.5mva 110kv Dual-Winding No-Load Tapping Power Transformer
12.5mva 35kv Arc Furnace Transformer 12500kVA Electric Arc Furnace Transformer
Popular Intelligent Resistor Monitoring Device Products
11kv 480oum Neutral Grounding Resistor Cabinet for Transformer
Popular Resistor Products
AC Zinc Oxide Varistor for 20-35kv Surge/Lightning Arrestor/Arrester D5-1
Metal Oxide Varistor/Resistor for Counter and Monitor Df-2
Metal/Zinc Oxide Varistor/Resistor for Low Voltage Surge/Lightning Arrestor/Arrester D1-2
AC Zinc Oxide Varistor for 330kv Surge/Lightning Arrestor/Arrester D8
AC Zinc Oxide Varistor for 500kv Surge/Lightning Arrestor/Arrester D13.6
Metal/Zinc Oxide Varistor/Resistor for Low Voltage Surge/Lightning Arrestor/Arrester D1-1