12kv High Voltage Drop out Fuses
12kv High Voltage Drop out Fuses image
Get Latest Price Request a quote
Quick Details
Product Details
kV to 38 kV grounded systems with 100 or 200 A nominal currents.
Especially designed to protect transformers, capacitors, cables or lines.
It is robust construction, made of rigorously tested material, will interrupt all faults under the
most severe conditions, maintaining mechanical and electric characteristics.
The inserts, hardware and structural bolts and nuts are made from heavy galvanized steel.
The Fuse Cutout type OEI can be applied on all three-phase system rated at or below the maximum
operational rating of the cutout.
| Performance Characteristic | |
| Applied standard | IEEE C37.42-2009 |
| Catalog number | |
| Nominal system voltage kV | 33 |
| Rated Frequency Hz | 50 |
| Rated m aximum(design) voltage | 38 |
| Rated Continuous current A-RMS | 100 |
| Rated Interrupting current asymmetrical/symmetrical A-RMS | 8000/5000 |
| BIL 1.2×50 µs kV-peak | 150 |
| Minimum critical impulse flashover voltage(CFO)KV peak | 165 |
| Dry withstand voltage kV-RMS | 70 |
| Wet withstand voltage kV-RMS | 60 |
| Creepage distance to group Min.mm | 650 |
| Minimum creepage factor of insulator (Creepage Distance/arcing distance) | 2.3 |
TABLE OF CONTENTS
ITEM TITLE PAGE
PART 1 GENERAL
1.01 SCOPE E13 1
1.02 STANDARDS E13 1
1.03 SERVICE CONDITIONS E13 2
1.04 SYSTEM CONDITIONS E13 2
1.05 TESTING E13 2
1.06 SPARES E13 3
1.07 PACKING AND SHIPMENT E13 3
1.08 SUBMITTALS E13 3
PART 2 PRODUCTS
2.01 DESIGN E13 4
A. Standardization of Fuse Links E13 4
B. Rating of Fuse Links E13 4
C. Characteristics of Fuse Links E13 4
2.02 MATERIALS E13 4
A. Current Carrying Parts of Fuse Links E13 4
B. Fuse Link Button E13 5
C. Length of Fuse Links E13 5
D. Pull on Fuse Links E13 5
E. Identification E13 5
TECHNICAL DATA SCHEDULE E13 6
1.01 SCOPE
This Specification covers the design, manufacturing, testing, supply, delivery and performance requirements of HV Expulsion Type Fuse Links for use by the Electricity Company of Ghana Limited.
1.02 STANDARDS
The fuse links shall comply with the latest editions of and amendments to, the standards/specifications listed below:
IEC – International Electrotechnical Commission
IEC 60282 – High Voltage Fuses Part 2: Expulsion and similar fuses
ANSI American National Standards Institute
IEEE C37.41 – Design for High Voltage Fuses, Distribution Enclosed Single Pole Air Switches. Fuse Disconnecting Switches and Accessories.
ANSI C37.42 – American National Standard Specifications for Distribution Cutouts and Fuse Links.
NEMA National Electrical Manufacturers Association
NEMA SG2 – High Voltage Fuses
1.03 SERVICE CONDITIONS
As in Specification H0C
1.04 SYSTEM CONDITIONS
As in Specification H0C
1.05 TESTING
Type Tests
A. The Supplier shall confirm on the attached schedule that the following tests have been performed according to ANSI C37.42.
1. Melting Current Tests; Table 6
2. Temperature Rise Tests
3. Time/Current Characteristic Tests
B. Type/Design Tests may (at the Purchaser’s discretion) be dispensed with if the Supplier/Contractor furnishes evidence to the Purchaser’s satisfaction that the relevant tests have already been performed on identical equipment. In this case the Supplier shall provide documentary proof in the form of Certified Test Certificates that the assembled equipment and its component parts been successfully typetested by an independent testing authority in accordance with the relevant clauses of referenced Standards. Test Certificates as evidence of successful completion of type tests shall be submitted as part of the Bid.
C. Inspection
1.06 SPARES
(NOT APPLICABLE)
1.07 PACKING AND SHIPMENT
As in Specification H0C
1.08 SUBMITTALS
As in Specification H0C
2.01 DESIGN
A. Standardization of Fuse Links (Mechanical/Interchangeable).
High voltage expulsion fuses shall be suitable for use on the Expulsion fusegears described in the associated specifications H16 and H34.
B. Rating of Fuse Links
The preferred rating of fuse links shall be 3A, 5A, 8A, 16A, 25A, 40A, 63A and 100A at 11kV and 1A, 2A, 3A, 5A, 8A, 16A, 20A and 31.5A at 33kV. The rated current of the fuse link is the maximum current which it will carry continuously without deterioration and undue heating. Supplier shall state on the attached schedule the maximum temperature in oC attained by the fuse link after continuous operation at maximum rating.
C. Performance Characteristics of Fuse Links
1. The fuse links are required to give protection against short circuits. They shall be so rated and shall have such blowing characteristics as to be suitable for selective operations with the fuse links at present in use on the system namely Type K i.e. fast, fuse links to NEMA SG2 and ANSI C37.42 1981.
2. The Supplier shall present to the Purchaser timecurrent characteristics of all the distribution fuselinks on offer. The performance characteristics of the fuselinks shall include:
(a) Meltingtimecurrent characteristics
(b) Total clearingtimecurrent
The timecurrent characteristics shall be presented as curves.
The Supplier shall state the minimum and maximum melting currents required to melt the fuse links at the three appropriate time points used in Table 6 {meltingcurrents for TypeK (fast) fuse links) of ANSI C37.42 1981
2.02 MATERIALS
A. Current carrying Parts of Fuse Links
All current carrying parts of the fuse links shall be nonferrous material; the main requirements being resistance to atmospheric corrosion. Tin is not acceptable as a possible element.
1. Fuse Element
2. Fuse Link
B. Fuse Link Button
The diameter of the button head cap on fuse links shall be 19.1mm. Removable type button heads are preferred for use with 11kV fusegear.
C. Length of Fuse Links
The minimum overall length of fuse links rated 1 to 100 amperes shall be:
: 510mm for 11kV units per ANSI C.37.42
: 762mm for 33kV units per ANSI C.37.42
D. Pull on Fuse Links (Tensile Withstand Strength)
The expulsion fusegear shall operate satisfactorily while exerting a pull of 44.5N on the fuse link per ANSI C.37.42, 3.2.3.4 1981.
E. Identification
Each fuse link must have stamped on it:
1. Manufacturers name or identifying mark
2. Continuous current rating
3. Type designation, K or T
We are China 12kv High Voltage Drop out Fuses manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Get Latest Price Request a quote
Popular Drop out Fuses Products
Standard High Voltage Cutout Distribution
Polymer Fuse Cutout, Drop out Fuses 24kv 200A
Channel Supporters Type Mgj, Group B
Polymer Fuse Cutout, Drop out Fuses 27kv 100A
Popular Fuse Cutout Products
33kv Fuse Cutout Approved by Kema Laboratory
33kv Outdoor High Quality Polymer Fuse Cutout
33kv High Voltage Porcelain Drop Fuse Cutout
36kv High Voltage Polymer Cutout Fuse, Drop-out Fusehrw12-36 Wind-Proof
Popular High Voltage Fuse Products
Interlock Liner Fully Dipped Blue Nitrile
PVC Gloves Sandy Finish Half/Full Green 35cm
Pcv Gloves with Long Sleeve Smooth/Sandy Finish Blue 60cm
Cut Resistance Gloves, Grade 3hppe + Dyneemagrey 7-11
Popular jgtrade1 Products
Wedged Insulation Strain Clamp
11kv Porcelain Line Post Insulators
Overload Protection High Voltage Expulsion Porcelain 11kv Drop-out Fuse Cutout
M16, 400mm Long Bolt Nut and Washer
Polymer Fuse Cutout, Drop out Fuses 15 Kv 100A
Tags: Drop out Fuses, Fuse Cutout, High Voltage Fuse, jgtrade1